Specifications Table for UATYP-AY1

UATYP850AMY1 UATYPC10AMY1 UATYPC12AMY1
Cooling capacity Nom. kW 82.939 (3) 101.110 (3) 109.609 (3)
Heating capacity Nom. kW 92.317 (3) 102.290 (3) 126.314 (3)
Power input Cooling Nom. kW 38.160 43.170 48.200
  Heating Nom. kW 34.780 41.670 46.800
EER 2.17 2.34 2.27
COP 2.65 2.45 2.70
Evaporator Supply side Fan Nominal ESP Pa 294 (0.000) 294 (0.000) 294 (0.000)
Evaporator piping connections Condensation drain size OD mm 25.4 25.4 25.4
Condenser Refrigerant Type   R-407C R-407C R-407C
    GWP   1,773.9 1,773.9 1,773.9
    Charge TCO2Eq 17 23.9 35.5
Dimensions Unit Height mm 1,735 1,974 1,974
    Width mm 2,250 2,252 2,252
    Depth mm 2,800 3,180 3,180
Weight Unit kg 1,350    
Casing Colour   Light grey Light grey Light grey
Power supply Name   Y1 Y1 Y1
  Phase   3~ 3~ 3~
  Frequency Hz 50 50 50
  Voltage V 380-415 380-415 380-415
Notes (1) - All specifications are subjected to change by the manufacturer without prior notice. (1) - All specifications are subjected to change by the manufacturer without prior notice. (1) - All specifications are subjected to change by the manufacturer without prior notice.
  (2) - All units are being tested and comply to ISO5151. (2) - All units are being tested and comply to ISO5151. (2) - All units are being tested and comply to ISO5151.
  (3) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB; Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (3) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB; Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (3) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB; Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB
  (4) - Sound pressure levels are according to JIS B 8615 standard. Position of the measurement is 1m in front and 1m below the unit. (4) - Sound pressure levels are according to JIS B 8615 standard. Position of the measurement is 1m in front and 1m below the unit. (4) - Sound pressure levels are according to JIS B 8615 standard. Position of the measurement is 1m in front and 1m below the unit.
  (5) - Designation based on cooling cycle. (5) - Designation based on cooling cycle. (5) - Designation based on cooling cycle.
  (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases