|
RXYSQ4T8VB9 |
RXYSQ5T8VB9 |
RXYSQ6T8VB9 |
Recommended combination |
3 x FXSQ25A2VEB + 1 x FXSQ32A2VEB |
4 x FXSQ32A2VEB |
2 x FXSQ32A2VEB + 2 x FXSQ40A2VEB |
Cooling capacity |
Prated,c |
kW |
12.1 (1) |
14.0 (1) |
15.5 (1) |
Heating capacity |
Prated,h |
kW |
8.0 |
9.2 |
10.2 |
SCOP |
4.4 |
4.6 |
4.9 |
SEER |
7.0 |
6.8 |
7.0 |
Space cooling |
A Condition (35°C - 27/19) |
EERd |
|
3.1 |
2.7 |
2.7 |
|
|
Pdc |
kW |
12.1 |
14.0 |
15.5 |
|
B Condition (30°C - 27/19) |
EERd |
|
5.3 |
4.9 |
4.9 |
|
|
Pdc |
kW |
8.9 |
10.3 |
11.4 |
|
C Condition (25°C - 27/19) |
EERd |
|
9.6 |
9.2 |
9.5 |
|
|
Pdc |
kW |
5.7 |
6.6 |
7.3 |
|
D Condition (20°C - 27/19) |
EERd |
|
14.0 |
15.3 |
16.4 |
|
|
Pdc |
kW |
4.3 |
4.5 |
4.6 |
Space heating (Average climate) |
TBivalent |
COPd (declared COP) |
|
2.6 |
2.6 |
2.7 |
|
|
Pdh (declared heating cap) |
kW |
8.0 |
9.2 |
10.2 |
|
|
Tbiv (bivalent temperature) |
°C |
-10 |
-10 |
-10 |
|
TOL |
COPd (declared COP) |
|
2.6 |
2.6 |
2.7 |
|
|
Pdh (declared heating cap) |
kW |
8.0 |
9.2 |
10.2 |
|
|
Tol (temperature operating limit) |
°C |
-10 |
-10 |
-10 |
|
A Condition (-7°C) |
COPd (declared COP) |
|
2.9 |
3.0 |
3.1 |
|
|
Pdh (declared heating cap) |
kW |
7.0 |
8.1 |
9.0 |
|
B Condition (2°C) |
COPd (declared COP) |
|
4.3 |
4.5 |
4.7 |
|
|
Pdh (declared heating cap) |
kW |
4.3 |
5.0 |
5.5 |
|
C Condition (7°C) |
COPd (declared COP) |
|
6.0 |
6.4 |
6.8 |
|
|
Pdh (declared heating cap) |
kW |
3.4 |
3.5 |
3.6 |
|
D Condition (12°C) |
COPd (declared COP) |
|
7.3 |
7.9 |
8.5 |
|
|
Pdh (declared heating cap) |
kW |
4.1 |
4.1 |
4.3 |
Capacity range |
HP |
4 |
5 |
6 |
Maximum number of connectable indoor units |
64 (3) |
64 (3) |
64 (3) |
Indoor index connection |
Min. |
|
50.0 |
62.5 |
70.0 |
|
Max. |
|
130.0 |
162.5 |
182.0 |
Dimensions |
Unit |
Height |
Mm |
1,345 |
1,345 |
1,345 |
|
|
Width |
Mm |
900 |
900 |
900 |
|
|
Depth |
Mm |
320 |
320 |
320 |
Weight |
Unit |
kg |
104 |
104 |
104 |
Compressor |
Type |
|
Hermetically sealed swing compressor |
Hermetically sealed swing compressor |
Hermetically sealed swing compressor |
Operation range |
Cooling |
Min. |
°CDB |
-5.0 |
-5.0 |
-5.0 |
|
|
Max. |
°CDB |
46.0 |
46.0 |
46.0 |
|
Heating |
Min. |
°CWB |
-20.0 |
-20.0 |
-20.0 |
|
|
Max. |
°CWB |
15.5 |
15.5 |
15.5 |
Sound power level |
Cooling |
Nom. |
dBA |
68.0 (4) |
69.0 (4) |
70.0 (4) |
Sound pressure level |
Cooling |
Nom. |
dBA |
50.0 (5) |
51.0 (5) |
51.0 (5) |
Refrigerant |
Type |
|
R-410A |
R-410A |
R-410A |
|
GWP |
|
2,087.5 |
2,087.5 |
2,087.5 |
|
Charge |
kg |
3.6 |
3.6 |
3.6 |
|
Charge |
TCO2Eq |
7.5 |
7.5 |
7.5 |
Piping connections |
Liquid |
Type |
|
Flare connection |
Flare connection |
Flare connection |
|
|
OD |
Mm |
9.52 |
9.52 |
9.52 |
|
Gas |
Type |
|
Flare connection |
Flare connection |
Braze connection |
|
|
OD |
Mm |
15.9 |
15.9 |
19.1 |
|
Total piping length |
System |
Actual |
m |
300 (6) |
300 (6) |
300 (6) |
Standard Accessories |
Installation manual |
1 |
1 |
1 |
|
Operation manual |
1 |
1 |
1 |
|
Connection pipes |
1 |
1 |
1 |
Power supply |
Name |
|
V1 |
V1 |
V1 |
|
Phase |
|
1N~ |
1N~ |
1N~ |
|
Frequency |
Hz |
50 |
50 |
50 |
|
Voltage |
V |
220-240 |
220-240 |
220-240 |
Notes |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m |
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m |
|
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). |
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). |
(3) - Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). |
|
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
(4) - Sound power level is an absolute value that a sound source generates. |
|
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
|
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
(6) - Refer to refrigerant pipe selection or installation manual |
|
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
|
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
(8) - MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
|
(9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
|
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
|
(11) - TOCA means the total value of each OC set. |
(11) - TOCA means the total value of each OC set. |
(11) - TOCA means the total value of each OC set. |
|
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
(12) - FLA means the nominal running current of the fan |
|
(13) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). |
(13) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). |
(13) - The automatic ESEER value corresponds with normal VRV IV-S heat pump operation, including the advanced energy saving functionality (variable refrigerant temperature control). |
|
(14) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. |
(14) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. |
(14) - The standard ESEER value corresponds with normal VRV IV-S heat pump operation, not taking into account the advanced energy saving functionality. |
|
(15) - Sound values are measured in a semi-anechoic room. |
(15) - Sound values are measured in a semi-anechoic room. |
(15) - Sound values are measured in a semi-anechoic room. |
|
(16) - Maximum allowable voltage range variation between phases is 2%. |
(16) - Maximum allowable voltage range variation between phases is 2%. |
(16) - Maximum allowable voltage range variation between phases is 2%. |
|
(17) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(17) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
(17) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
|
(18) - For detailed contents of standard accessories, see installation/operation manual |
(18) - For detailed contents of standard accessories, see installation/operation manual |
(18) - For detailed contents of standard accessories, see installation/operation manual |
|
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
(19) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and ≤ 75A per phase |
|
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |
(20) - Ssc: Short-circuit power |