FUA71AVEB / RZQG71L9V1B FUA100AVEB / RZQG71L9V1B FUA100AVEB / RZQG100L9V1B FUA125AVEB / RZQG125L9V1B
Cooling capacity Nom. kW 6.80 6.80 9.50 12.00
  Nom. Btu/h 23,200 23,203 32,400 40,900
  Nom. kcal/h 5,847 5,847 8,169 10,318
Heating capacity Nom. kW 7.50   10.80 13.50
  Nom. Btu/h 25,600   36,900 46,100
  Nom. kcal/h 6,449   9,286 11,608
Power input Cooling Nom. kW 1.67 1.67 2.33 3.53
  Heating Nom. kW 1.84   2.73 3.95
Nominal efficiency EER   4.07 4.07 4.08 3.40
  COP   4.08   3.95 3.42
  Annual energy consumption kWh 835   1,164 1,765
  Energy labeling Directive Cooling   A   A A
    Heating   A   A B
Space cooling Energy efficiency class   A++ A++ A++ A+
  Capacity Pdesign kW 6.80 6.80 9.50 12.00
  SEER   6.42 6.42 6.11 5.61
  Annual energy consumption kWh/a 371 371 545 749
  A Condition (35°C - 27/19) Pdc kW 6.80 6.80 9.50 12.00
    EERd   4.07 4.07 4.08 3.40
    Power input kW 1.67 1.67 2.33 3.53
  B Condition (30°C - 27/19) Pdc kW 5.16 5.16 7.08 8.84
    EERd   4.63 4.63 4.51 4.35
    Power input kW 1.11 1.11 1.57 2.03
  C Condition (25°C - 27/19) Pdc kW 4.01 4.01 5.64 5.86
    EERd   8.61 8.61 7.88 6.76
    Power input kW 0.47 0.47 0.72 0.87
  D Condition (20°C - 27/19) Pdc kW 4.17 4.17 5.85 5.57
    EERd   11.42 11.42 10.08 8.68
    Power input kW 0.37 0.37 0.58 0.64
Space heating (Average climate) Energy efficiency class   A+ A+ A+ A+
  Capacity Pdesign kW 7.60 7.60 11.30 14.13
  SCOP/A   4.20 4.20 4.50 4.44
  SCOPnet/A   4.22 4.22 4.53 4.47
  Pdh Heating capacity at -10° kW 6.66 6.66 9.63 12.19
  Annual energy consumption kWh/a 2,534 2,534 3,516 4,456
  Required back up heating cap at design conditions kW 0.94 0.94 1.67 1.94
  TOL Tol (temperature operating limit) °C -15 -15 -15 -15
    Pdh (declared heating cap) kW 6.55 6.55 9.01 11.67
    COPd (declared COP)   2.22 2.22 2.71 1.99
    Power input kW 2.95 2.95 3.32 5.86
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -7 -7
    Pdh (declared heating cap) kW 6.72 6.72 10.00 12.50
    COPd (declared COP)   2.99 2.99 3.63 2.89
    Power input kW 2.25 2.25 2.75 4.33
  A Condition (-7°C) Pdh (declared heating cap) kW 6.72 6.72 10.00 12.50
    COPd (declared COP)   2.99 2.99 3.63 2.89
    Power input kW 2.25 2.25 2.75 4.33
  B Condition (2°C) Pdh (declared heating cap) kW 4.09 4.09 6.26 7.61
    COPd (declared COP)   3.76 3.76 3.92 4.00
    Power input kW 1.09 1.09 1.60 1.90
  C Condition (7°C) Pdh (declared heating cap) kW 2.90 2.90 4.12 4.89
    COPd (declared COP)   6.22 6.22 6.33 6.81
    Power input kW 0.47 0.47 0.65 0.72
  D Condition (12°C) Pdh (declared heating cap) kW 3.30 3.30 4.71 5.38
    COPd (declared COP)   7.25 7.25 7.40 7.82
    Power input kW 0.46 0.46 0.64 0.69
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW 0.000 0.000 0.000 0.000
    Heating PCK kW 0.000 0.000 0.000 0.000
  Off mode Cooling POFF kW 0.009 0.009 0.009 0.009
    Heating POFF kW 0.009 0.009 0.009 0.009
  Standby mode Cooling PSB kW 0.009 0.009 0.009 0.009
    Heating PSB kW 0.009 0.009 0.009 0.009
  Thermostat-off mode Cooling PTO kW 0.007 0.007 0.009 0.009
    Heating PTO kW 0.007 0.007 0.009 0.009
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25 0.25
Cooling function included Yes Yes Yes Yes
Heating function included Yes Yes Yes Yes
Average climate included Yes Yes Yes Yes
Cold season included No No No No
Warm season included No No No No
Eurovent Sound power level outdoor Cooling Nom. dBA 64 64 66 67
  Sound power level indoor Cooling Nom. dBA 59 64 64 65
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - See separate drawing for operation range (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - See separate drawing for electrical data (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range   (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data   (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data