Specifications Table for FNA-A / RXM-M9

FNA25A2VEB / RXM25M3V1B9 FNA35A2VEB / RXM35M3V1B9 FNA50A2VEB / RXM50M3V1B9 FNA60A2VEB / RXM60M3V1B9
Cooling capacity Nom. kW 2.60 3.40 5.00 6.00
Heating capacity Nom. kW 3.20 4.00 5.80 7.00
Nominal efficiency EER   3.80 3.09 3.38 2.70
  COP   4.00 3.48 3.34 3.11
  Annual energy consumption kWh 342 551 739 1,111
  Energy labeling Directive Cooling   A B A D
    Heating   A B C D
Space cooling Energy efficiency class   A+ A+ A+ A
  Capacity Pdesign kW 2.60 3.40 5.00 6.00
  SEER   5.68 5.70 5.77 5.56
  Annual energy consumption kWh/a 160 209 303 378
Space heating (Average climate) Energy efficiency class   A+ A+ A+ A+
  Capacity Pdesign kW 2.80 2.90 4.00 4.60
  SCOP/A   4.24 4.05 4.09 4.16
  Annual energy consumption kWh/a 924 1,002 1,369 1,547
Notes (1) - See separate drawing for electrical data (1) - See separate drawing for electrical data (1) - See separate drawing for operation range (1) - See separate drawing for operation range
  (2) - See separate drawing for operation range (2) - See separate drawing for operation range (2) - See separate drawing for electrical data (2) - See separate drawing for electrical data
  (3) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (3) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (3) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (3) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (4) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (4) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (4) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (4) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.