FHA100AVEB / RZAG71M7V1B FHA71AVEB / RZAG71M7V1B FHA100AVEB / RZAG100M7V1B FHA140AVEB / RZAG100M7V1B FHA125AVEB / RZAG125M7V1B FHA140AVEB / RZAG140M7V1B
Indoor unit FHA100AVEB FHA71AVEB FHA100AVEB FHA140AVEB FHA125AVEB FHA140AVEB
Outdoor unit RZAG71M7V1B RZAG71M7V1B RZAG100M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B
Cooling capacity Nom. kW 6.80 (1) 6.80 (1) 9.50 (1) 9.50 (1) 12.1 (1) 13.4 (1)
Heating capacity Nom. kW 7.50 (2) 7.50 (2) 10.8 (2) 10.8 (2) 13.5 (2) 15.5 (2)
Space cooling Energy efficiency class A++ A++ A++ A++    
  Capacity Pdesign kW 6.80 6.80 9.50 9.50 12.1 13.4
  SEER 6.69 7.11 6.42 8.24 8.22 6.42
  ηs,c %         326 254
  Annual energy consumption kWh/a 356 335 518 404 883 1,252
  A Condition (35°C - 27/19) Pdc kW 6.80 6.80 9.50 9.50 12.10 13.40
    EERd 4.28 4.14 4.86 4.85 4.11 2.98
    Power input kW 1.59 1.64 1.95 1.96 2.94 4.49
  B Condition (30°C - 27/19) Pdc kW 5.02 5.02 7.00 7.00 8.92 9.88
    EERd 5.91 6.08 4.83 6.74 6.48 5.08
    Power input kW 0.85 0.83 1.45 1.04 1.38 1.94
  C Condition (25°C - 27/19) Pdc kW 3.23 3.37 4.50 4.50 5.74 6.35
    EERd 8.41 9.25 7.82 10.04 9.53 7.28
    Power input kW 0.38 0.36 0.58 0.45 0.60 0.87
  D Condition (20°C - 27/19) Pdc kW 3.11 3.44 4.20 4.50 4.43 4.04
    EERd 9.77 11.02 9.91 14.11 13.71 10.96
    Power input kW 0.32 0.31 0.42 0.32 0.32 0.37
Space heating (Average climate) Energy efficiency class A+ A+ A++ A++    
  Capacity Pdesign kW 4.70 4.70 7.80 7.80 9.52 9.52
  SCOP/A 4.26 4.32 4.61 4.64 4.09 4.30
  SCOPnet/A 4.26 4.32 4.61 4.64 4.09 4.30
  ηs,h %         161 169
  Annual energy consumption kWh/a 1,545 1,523 2,369 2,353 3,259 3,100
  Required back up heating cap at design conditions kW 0.00 0.00 0.00 0.00 0.00 0.00
  TOL Tol (temperature operating limit) °C -10 -10 -10 -10 -10 -10
    Pdh (declared heating cap) kW 4.70 4.70 7.80 7.80 9.52 9.52
    COPd (declared COP) 2.56 2.40 2.28 2.47 1.72 2.00
    Power input kW 1.84 1.95 3.42 3.16 5.54 4.76
  TBivalent Tbiv (bivalent temperature) °C -10 -10 -10 -10 -10 -10
    Pdh (declared heating cap) kW 4.70 4.70 7.80 7.80 9.52 9.52
    COPd (declared COP) 2.56 2.40 2.28 2.47 1.72 2.00
    Power input kW 1.84 1.95 3.42 3.16 5.54 4.76
  A Condition (-7°C) Pdh (declared heating cap) kW 4.16 4.16 6.90 6.90 8.42 8.42
    COPd (declared COP) 2.91 2.78 2.81 2.47 2.20 2.44
    Power input kW 1.43 1.50 2.45 2.79 3.83 3.45
  B Condition (2°C) Pdh (declared heating cap) kW 2.53 2.53 4.20 4.20 5.12 5.13
    COPd (declared COP) 4.36 4.41 4.82 5.00 4.38 4.64
    Power input kW 0.58 0.57 0.87 0.84 1.17 1.11
  C Condition (7°C) Pdh (declared heating cap) kW 2.15 2.08 2.75 2.89 3.46 3.30
    COPd (declared COP) 5.27 5.55 5.58 5.75 5.21 5.17
    Power input kW 0.41 0.37 0.49 0.50 0.66 0.64
  D Condition (12°C) Pdh (declared heating cap) kW 2.54 2.51 3.20 3.44 4.06 3.42
    COPd (declared COP) 6.58 6.86 7.17 7.26 6.38 6.46
    Power input kW 0.39 0.37 0.45 0.47 0.64 0.53
Power consumption in other than active mode Thermostat-off mode PTO Heating W         12 12
      Cooling W         0 0
  Standby mode Cooling PSB W 12 12 12 12 12 12
    Heating PSB W 12 12 12 12 12 12
  Crankcase heater mode PCK W 0 0 0 0 0 0
  Off mode POFF W 12 12 12 12 12 12
Pto (Thermostat off) W 12, 0 12, 0 12, 0 12, 0    
Indication if the heater is equipped with a supplementary heater (pair application)         No No
Cooling Cdc (Degradation cooling) 0.25 0.25 0.25 0.25 0.25 0.25
Heating Cdh (Degradation heating) 0.25 0.25 0.25 0.25 0.25 0.25
Cooling function included Yes Yes Yes Yes Yes Yes
Heating function included Yes Yes Yes Yes Yes Yes
Average climate included Yes Yes Yes Yes Yes Yes
Cold season included No No No No No No
Warm season included No No No No No No
Ecolabel logo No No No No No No
Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W] Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W] Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
  Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.