FCAG35BVEB / RXM35N2V1B9 FCAG35BVEB / RXM35N5V1B9 FCAG50BVEB / RXM50N2V1B9 FCAG60BVEB / RXM60N2V1B9
Indoor unit FCAG35BVEB FCAG35BVEB FCAG50BVEB FCAG60BVEB
Outdoor unit RXM35N2V1B9 RXM35N5V1B9 RXM50N2V1B9 RXM60N2V1B9
Cooling capacity Nom. kW 3.50 3.50 5.00 5.70
  Nom. Btu/h 11,900 11,900 17,100 19,400
  Nom. kcal/h 3,009 3,009 4,299 4,901
Heating capacity Nom. kW 4.20 4.20 6.00 7.00
  Nom. Btu/h 14,300 14,300 20,500 23,900
  Nom. kcal/h 3,611 3,611 5,159 6,019
Power input Cooling Nom. kW 0.94 0.94 1.40 1.72
  Heating Nom. kW 1.11 1.11 1.62 2.07
Nominal efficiency EER   3.72 3.72 3.58 3.31
  COP   3.77 3.77 3.70 3.38
  Annual energy consumption kWh 470 470 698 861
  Energy labeling Directive Cooling   A A A A
    Heating   A A A C
Space cooling Energy efficiency class   A++ A++ A++ A++
  Capacity Pdesign kW 3.50 3.50 5.00 5.70
  SEER   6.35 6.35 6.54 6.40
  Annual energy consumption kWh/a 193 193 266 312
  A Condition (35°C - 27/19) Pdc kW 3.50 3.50 5.00 5.68
    EERd   3.72 3.72 3.58 3.31
    Power input kW 0.94 0.94 1.40 1.72
  B Condition (30°C - 27/19) Pdc kW 2.60 2.60 3.67 4.16
    EERd   5.33 5.33 5.17 4.67
    Power input kW 0.49 0.49 0.71 0.89
  C Condition (25°C - 27/19) Pdc kW 1.68 1.68 2.37 2.70
    EERd   9.52 9.52 8.52 7.87
    Power input kW 0.18 0.18 0.28 0.34
  D Condition (20°C - 27/19) Pdc kW 1.49 1.49 1.87 1.62
    EERd   12.25 12.25 10.69 12.03
    Power input kW 0.12 0.12 0.17 0.13
Space heating (Average climate) Energy efficiency class   A++ A++ A+ A+
  Capacity Pdesign kW 3.32 3.32 4.36 4.71
  SCOP/A   4.90 4.90 4.30 4.20
  SCOPnet/A   4.96 4.96 4.33 4.22
  Pdh Heating capacity at -10° kW 2.60 2.60 3.87 4.12
  Annual energy consumption kWh/a 948 948 1,419 1,569
  Required back up heating cap at design conditions kW 0.72 0.72 0.49 0.59
  TOL Tol (temperature operating limit) °C -15 -15 -15 -15
    Pdh (declared heating cap) kW 2.04 2.04 3.89 4.04
    COPd (declared COP)   2.50 2.50 2.04 2.08
    Power input kW 0.82 0.82 1.91 1.94
  TBivalent Tbiv (bivalent temperature) °C -7 -7 -7 -7
    Pdh (declared heating cap) kW 2.94 2.94 3.86 4.17
    COPd (declared COP)   3.10 3.10 2.81 2.56
    Power input kW 0.95 0.95 1.37 1.63
  A Condition (-7°C) Pdh (declared heating cap) kW 2.94 2.94 3.86 4.17
    COPd (declared COP)   3.10 3.10 2.81 2.56
    Power input kW 0.95 0.95 1.37 1.63
  B Condition (2°C) Pdh (declared heating cap) kW 1.79 1.79 2.34 2.53
    COPd (declared COP)   4.98 4.98 4.38 4.30
    Power input kW 0.36 0.36 0.53 0.59
  C Condition (7°C) Pdh (declared heating cap) kW 1.15 1.15 1.54 1.64
    COPd (declared COP)   6.20 6.20 5.31 5.28
    Power input kW 0.19 0.19 0.29 0.31
  D Condition (12°C) Pdh (declared heating cap) kW 1.24 1.24 1.79 1.46
    COPd (declared COP)   7.88 7.88 6.47 6.51
    Power input kW 0.16 0.16 0.28 0.22
Space heating (Warm climate) Energy efficiency class   A+++ A+++ A+++ A+++
  Capacity Pdesignh kW 1.79 1.79 2.34 2.53
  SCOP   6.27 6.27 5.26 5.36
  SCOPnet   6.36 6.36 5.31 5.41
  Annual energy consumption kWh/a 400 400 623 661
  Required back up heating cap at design conditions kW 0.00 0.00 0.00 0.00
  TOL Tol (temperature operating limit) °C -15 -15 -15 -15
    Pdh (declared heating cap) kW 2.04 2.04 3.89 4.04
    COPd (declared COP)   2.50 2.50 2.04 2.08
    Power input kW 0.82 0.82 1.91 1.94
  TBivalent Tbiv (bivalent temperature) °C 2 2 2 2
    Pdh (declared heating cap) kW 1.79 1.79 2.34 2.53
    COPd (declared COP)   4.98 4.98 4.38 4.30
    Power input kW 0.36 0.36 0.53 0.59
  B Condition (2°C) Pdh (declared heating cap) kW 1.79 1.79 2.34 2.53
    COPd (declared COP)   4.98 4.98 4.38 4.30
    Power input kW 0.36 0.36 0.53 0.59
  C Condition (7°C) Pdh (declared heating cap) kW 1.15 1.15 1.54 1.64
    COPd (declared COP)   6.20 6.20 5.31 5.28
    Power input kW 0.19 0.19 0.29 0.31
  D Condition (12°C) Pdh (declared heating cap) kW 1.24 1.24 1.79 1.46
    COPd (declared COP)   7.88 7.88 6.47 6.51
    Power input kW 0.16 0.16 0.28 0.22
Power consumption in other than active mode Crankcase heater mode Cooling PCK kW 0.000 0.000 0.000 0.000
    Heating PCK kW 0.000 0.000 0.000 0.000
  Off mode Cooling POFF kW 0.014 0.014 0.007 0.007
    Heating POFF kW 0.014 0.014 0.007 0.007
  Standby mode Cooling PSB kW 0.014 0.014 0.007 0.007
    Heating PSB kW 0.014 0.014 0.007 0.007
  Thermostat-off mode Cooling PTO kW 0.007 0.007 0.007 0.007
    Heating PTO kW 0.007 0.007 0.007 0.007
Cooling Cdc (Degradation cooling)   0.25 0.25 0.25 0.25
Heating Cdh (Degradation heating)   0.25 0.25 0.25 0.25
Cooling function included Yes Yes Yes Yes
Heating function included Yes Yes Yes Yes
Average climate included Yes Yes Yes Yes
Cold season included No No No No
Warm season included Yes Yes Yes Yes
Eurovent Sound power level outdoor Cooling Nom. dBA 61 61 62 63
  Sound power level indoor Cooling Nom. dBA 49 49 49 51
  Piping length Cooling Measuring condition m 5.00 5.00 5.00 5.00
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data