Specifications Table for FBA-A / RZAG-MV1

FBA100A2VEB / RZAG71M7V1B FBA100A2VEB / RZAG100M7V1B FBA140A2VEB / RZAG100M7V1B FBA125A2VEB / RZAG125M7V1B FBA140A2VEB / RZAG140M7V1B FBA71A2VEB / RZAG71M7V1B (Archived)
Cooling capacity Nom. kW 6.80 (1) 9.50 (1) 9.50 (1) 12.1 (1) 13.4 (1) 6.80 (1)
Heating capacity Nom. kW 7.50 (2) 10.8 (2) 10.8 (2) 13.5 (2) 15.5 (2) 7.50 (2)
Space cooling Energy efficiency class           A++
  Capacity Pdesign kW           6.80
  SEER           6.22
  Annual energy consumption kWh/a           382
Space heating (Average climate) Energy efficiency class           A+
  Capacity Pdesign kW           4.70
  SCOP/A           4.20
  Annual energy consumption kWh/a           1,566
Pto (Thermostat off) W 14, 0 14, 0 14, 0      
Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W] Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (1) - Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB [Btu/hr/W]
  Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.