FAQ100CVEB9 / RZQG71L9V1B |
FAQ71CVEB9 / RZQG71L9V1B |
FAQ100CVEB9 / RZQG100L9V1B |
Poff (Off mode) |
W |
0.0 |
|
0.0 |
Cooling |
Psb (Standby mode cooling) |
W |
7.0 |
|
9.0 |
|
Cooling-=-Cooling cdc degradation cooling |
0.25 |
|
0.25 |
Eurovent |
Sound power level indoor |
Cooling |
Nom. |
dBA |
65 |
|
65 |
|
Sound power level outdoor |
Cooling |
Nom. |
dBA |
64 |
|
66 |
Seasonal efficiency (according to EN14825) |
Cooling |
Pdesign |
kW |
6.80 |
|
9.50 |
|
|
Annual energy consumption |
kWh |
366 |
|
545 |
|
|
Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class |
6.51 |
|
6.11 |
|
|
D Condition (20°C - 27/19) |
Pdc |
kW |
3.97 |
|
5.53 |
|
|
|
power input |
kW |
0.33 |
|
0.53 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd |
12.19 |
|
10.56 |
|
|
C Condition (25°C - 27/19) |
power input |
kW |
0.42 |
|
0.65 |
|
|
|
Pdc |
kW |
3.86 |
|
5.40 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd |
9.26 |
|
8.31 |
|
|
A Condition (35°C - 27/19) |
power input |
kW |
2.00 |
|
2.63 |
|
|
|
Pdc |
kW |
6.80 |
|
9.50 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd |
3.40 |
|
3.62 |
|
|
B Condition (30°C - 27/19) |
Pdc |
kW |
5.08 |
|
7.00 |
|
|
|
power input |
kW |
1.18 |
|
1.67 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd |
4.33 |
|
4.20 |
|
Heating (Average climate) |
Annual energy consumption |
kWh |
2,205 |
|
3,562 |
|
|
Pdh Heating capacity at -10° |
kW |
5.93 |
|
8.8 |
|
|
Pdesign |
kW |
6.33 |
|
10.20 |
|
|
Required back up heating cap at design conditions |
kW |
0.40 |
|
1.40 |
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scopnet a |
A+ |
|
A+ |
|
|
TBivalent |
Pdh (declared heating cap) |
kW |
5.60 |
|
9.02 |
|
|
|
Power input |
kW |
2.03 |
|
2.83 |
|
|
|
Tbiv (bivalent temperature) |
°C |
-7 |
|
-7 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop |
2.77 |
|
3.19 |
|
|
C Condition (7°C) |
Pdh (declared heating cap) |
kW |
2.88 |
|
4.02 |
|
|
|
Power input |
kW |
0.45 |
|
0.67 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop |
6.45 |
|
6.07 |
|
|
TOL |
Tol (temperature operating limit) |
°C |
-15 |
|
-15 |
|
|
|
Pdh (declared heating cap) |
kW |
6.48 |
|
8.43 |
|
|
|
Power input |
kW |
3.28 |
|
3.77 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop |
1.98 |
|
2.24 |
|
|
A Condition (-7°C) |
Pdh (declared heating cap) |
kW |
5.60 |
|
9.02 |
|
|
|
Power input |
kW |
2.03 |
|
2.83 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop |
2.77 |
|
3.19 |
|
|
D Condition (12°C) |
Pdh (declared heating cap) |
kW |
3.27 |
|
4.58 |
|
|
|
Power input |
kW |
0.45 |
|
0.66 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop |
7.41 |
|
6.94 |
|
|
B Condition (2°C) |
Power input |
kW |
1.20 |
|
1.75 |
|
|
|
Pdh (declared heating cap) |
kW |
4.52 |
|
5.96 |
|
|
|
Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop |
3.77 |
|
3.41 |
Cooling capacity |
Nom. |
kW |
|
6.8 |
9.5 |
Pck (Crankcase heater mode) |
W |
0.0 |
|
0.0 |
Nominal efficiency |
Annual energy consumption |
kWh |
|
1,000 (0.000) |
1,315 (0.000) |
Heating |
Psb (Standby mode heating) |
W |
7.0 |
|
9.0 |
|
Heating-=-Heating cdh degradation heating |
0.25 |
|
0.25 |
Heating capacity |
Nom. |
kW |
|
7.5 |
10.8 |
Pto (Thermostat off) |
W |
7.0 |
7.0 |
9.0 |
Power input |
Cooling |
Nom. |
kW |
|
|
2.63 |
|
Heating |
Nom. |
kW |
|
|
3.00 |
Cold season included |
Yes |
|
Yes |
Notes |
Notes-=-Description |
EER/COP according to Eurovent 2012, for use outside EU only |
|
|
Nominal efficiency |
EER |
|
|
3.40 |
|
|
COP |
|
|
3.70 |
|
|
Energy labeling Directive |
Cooling |
|
|
A |
|
|
|
Heating |
|
|
A |
|
Notes |
|
Annual energy consumption is according to Energy labeling directive 2002/31/EC |
EER/COP according to Eurovent 2012, for use outside EU only |
|
|
SEER and SCOP are according to EN 14825 |
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load |
Nominal efficiency |
Energy labeling Directive |
Heating |
|
|
A |
|
Nominal efficiency-=-Cop |
|
|
3.62 |